CPCE 12 Flare : 034N0081

฿0.00

 

Model : CPCE 12 Flare : 034N0081
Pressure setting and adjust : 0- 86 psig
Factory Setting : 5.8 psig
Connection : Flare connection
Size : 1/2″
SKU: CPCE 12 Flare : 034N0081 Categories: , , Brand:

Description

Type Connection Rated capacity (1)[kW] Code no.
Flare Flare Solder R22 R134a R404A/R507 R407C
[in] [in]   [mm]
CPCE 12 1/2 12 17.4 7.9 16.4 19.0 034N0081
CPCE 12 12 12 17.4 7.9 16.4 19.0 034N0082
CPCE 15 5/8 16 25.6 11.6 24.2 27.9 034N0083
CPCE 22 7/8 22 34.0 15.2 32.0 37.1 034N0084
The rated capacity is the regulator capacity at:
– evaporating temperature te = -10 °C,- condensing temperature tc = 30 °C,- reduction of suction temperature / suction pressure ∆t s = 4 K.
.

CPCE

CPCE hot gas bypass regulator adapt
compressor capacity to actual evaporator load.
They are designed for installation in a bypass
line between the low and high pressure sides of
the refrigeration system, for hot gas injection
between the evaporator and thermostatic
expansion valve.
Refrigerants R22, R1234ze *), R1270 *), R134a, R290 *), R404A, R407A, R407C, R407F, R448A, R449A, R450A, R452A, R507A, R513A, R600 *),
R600a *)
Regulating range 0 to 87 psig
Factory setting = 8.5 psig
Maximum working pressure between the evaporator and thermostatic
Maximum test pressure MWP = 406 psig
Maximum differential pressure Δp = 18 bar
Maximum media temperature 140 °C
Minimum media temperature -50 °C
 

 

 

Leave a Reply

Your email address will not be published. Required fields are marked *