KVR 28 : 034L0095

฿0.00

 

Model : KVR 28 : 034L0095
Pressure setting and adjust : 73 – 254 psig
Factory Setting : 145 psig
Connection : solder connection
Size : 1-1/8″
SKU: KVR 28 : 034L0095 Categories: , , Brand:

Description

Type Rated liquid capacity (1) (Evaporator ca-pacity) [kW] Rated hot gas (1) (Evaporator capacity) [kW] Flare connect. (2) Code no. Solder Connect. Code no.
R22 R134a R404A/ R507 R407C R22 R134a R404A/ R507 R407C [in] [mm] [in] [mm]
KVR 12 50.4 47.3 36.6 54.4 13.2 11.6 12 14.3 1⁄2 12 034L0091 1⁄2 034L0093
50.4 47.3 36.6 54.4 13.2 11.6 12 14.3 12 034L0096
KVR 15 50.4 47.3 36.6 54.4 13.2 11.6 12 14.3 5⁄8 16 034L0092 5⁄8 16 034L0097
KVR 22 50.4 47.3 36.6 54.4 13.2 11.6 12 14.3 7⁄8 22 034L0094
KVR 28 129 121 93.7 139.3 34.9 30.6 34.9 37.7 1-1/8 034L0095
129 121 93.7 139.3 34.9 30.6 34.9 37.7 28 034L0099
KVR 35 129 121 93.7 139.3 34.9 30.6 34.9 37.7 1-3/8 35 034L0100
KVR The condensing pressure regulator, type KVR
can be mounted in either the gas or liquid
side of the condenser in refrigeration and air
conditioning systems.
They are used to maintain a constant and
sufficiently high condensing pressure with
systems using air-cooled condensers.
They can also be used with valve types NRD
or KVD to assure that adequate pressure is
maintained on the receiver.
Refrigerants R22, R32**, R134a, R290*, R404A, R407A, R407C, R407F, R407H, R410A**, R448A, R449A, R449B, R450A, R452A, R452B**, R454A*, R454B**, R454C*, R455A*, R507, R513A, R515B, R516A, R600*, R600a*, R1233zd(E)**, R1234ze(E)*, R1234yf*,
R1270* *KVR 12 – KVR 22 only;
Adjustment range Pe = 73.00 – 254.00 psig
Factory setting = 145 psig
Maximum working pressure KVR: PS/MWP = 406 psig
NRD: PS/MWP = 667 psig
Maximum test pressure KVR: Pe = 450 psig
NRD: Pe = 870 psig
Medium temperature range KVR: -45 – 130 °C,
NRD: -50 – 155 °C
P-band KVR 12 – 22: 90 psi
KVR 28 – 35: 72.5 psi
Minimum opening pressure differential for NRD Start opening: Δp = 1.4 bar